96V 6500i

Technical Specifications

MODEL HAUS STROM Series HPSW 6500i
VOLTAGE LIMITS NARROW WINDOW(UPS MODE)
Mains A.c Low Cut 180±10V
Mains A.C Low Cut Recovery 9-12V Hysterisis from
>Low Cut Voltage
Mains A.C High Cut 260±10V
Mains A.C High Cut Recovery 9-12V Hysterisis from
< High Cut Voltage
VOLTAGE LIMITS WIDE WINDOW(W-UPS MODE)
Mains A.C Low Cut 100±10V
Mains A.C Low Cut Recovery 9-12V Hysterisis
>LowCut Voltage
Mains A.C High Cut 280±10V
Mains A.C High Cut Recovery 9-12V Hysterisis
< HighCut Voltage
OUTPUT PARAMETER
Mains Output Same as Input (45Hz-55Hz)
Output Frequency 50Hz±1Hz
Output Voltage With Full Load 177-220V
Waveform Sine Wave
Overload Above 100%
Short Circuit Protecon >200%
MODEL HAUS STROM Series HPSW 6500i
BATTERY CHARGING
Closed Loop Auto Sensing Sftoware Control(ASSC) Charging Technology with over full range of Mains 100V-280V±10V
Battery type SMF/TUBULAR/Flooded LEAD ACID (Selectable )
Charging Current 18A/13A(Selectable)
Recommended Baery Capacity 100-200AH
Number of Baeries 8
TECHNOLOGY
Pure Sine Wave Technology using PWM Topology
Closed Loop Auto Sensing Soware Control(ASSC) Smart Power Storage Charging
Technology for Longer Power Storage Life
Storage Temp. 0-50˚C
Operang Temp. 0-40˚C
Humidity 90%Non -Condensing
Dimension (WXDXH) in mm 000x000x000mm

ALL GENERATORS COMPATIBLE

Haus Strom Inverter can charge batteries with power provided by all kinds of generators local or company made. Wide window of frequency range between 45-55Hz makes totally compatible with all local generators.

TRUE GALVANIC ISOLATION

Fundamental frequency transformer is used for low frequency isolation at the grid side. It provides safety to equipment against power surges & transients.

COMPATIBLE WITH WIDEST RANGE OF BATTERIES

Haus Strom inverter 5 KVA / 48 V is able to charge batteries of all sizes. This feature give you the flexibility to buy the battery that is suited to your background.

BYPASS FEATURE

Incase of maintenance of the battery/failure of Haus Strom Inverter or during the servicing of the UPS, the costumer himself can directly switch to the mains by a simple twist of a switch, and will not need any electrician to remove any wires from the inverter.